Cover with spacer is extra deep for applications with an exposed back junction box and or conduit.
Fire alarm pull station height ada.
Below we have an picture of a typical manual pull station.
Under the ada audible alarms must have a sound level that is not greater than 110 db.
Install these to protect your fire alarm stations from damage.
Nfpa 72 standards state that the operable part of the pull station shall be between 3 1 3 ft and 4 1 2 ft.
Covers help comply with ada standards when properly installed.
In addition the pull lever should be within reach range or between 48 inches and 15 inches above the finish floor or ground.
If the path to the ada compliant fire extinguisher or pull station is unobstructed the operable part must be placed from 15 inches to 48 inches off of the finished floor or ground.
In addition the requirements for visible fire alarms are required to meet the following standards.
Manual fire alarm boxes pull stations the height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 54 inches measured vertically from the floor level to the activating handle or lever of the box.
To the best of my knowledge ada says to follow nfpa 72 standards.
Where i live we are subject to ada americans with disabilites act and it requires manual pull stations and other things containing an operable control like light switches to be mounted at 48.
Manual fire alarm boxes mounted with the top of the.
Manual fire alarm boxes shall be red in color.
An alarm sounds when the cover is lifted.
According to the adaag manual fire alarm boxes must be mounted not more than 48 inches high for front reach and 54 inches high for side reach.